FCC 1000W - Single Zone Fire Alarm Controls


Features:
•   Monitored detector zone for use with smoke detectors, heat detectors and
    manual call points
•   Two fused sounder circuits, monitored for open and short circuits
•   Mutable fault monitoring for mains, power supply unit, battery, sounders and
    detectors
•   500 mA power supply unit, with space for up to 4.2 A.H. sealed lead acid
    batteries
•   High brightness dual LED indicators
•   Touch sensitive controls
•   This single zone control has been designed to conform with the requirements
    of BS 3116 and BS 5839
•   For ease of installation and service, connections are made to a small rear mounted printed circuit board
    that also holds the battery and sounder fuses. The metal case has three point key-slot fixing with 20 mm
    conduit trunking top and bottom entry points
•   The detection zone is monitored with an end of line resistor to give fault and fire indications. They will
    monitor upto 35 low current smoke detectors and an infinite number of manual call points or other OC
    devices
•   The sounder circuits are fused and monitored for open and short circuits with an end of line resistor. Upto     20 low current sounders (25 mA) may be fitted
•   The power supply is fully monitored for failure, mains failure, battery failure, low voltage and battery
    disconnection
•   The user controls are enabled by means of a security keyswitch
•   Mute Sounders - mutes sounders and fault warning
•   Sound Alarm - to evacuate building or resound alarm
•   Reset (Test) - to reset control and detectors and test control
•   Indications are provided for mains power, zone fire, zone fault, sounder fault and power fault
•   Audible indications are provided for fire and fault
•   Printed circuit boards are available as new for spares

FCC 2000W - Two Zone Fire Alarm Controls


Features:
•   Monitored detector zones for use with smoke detectors, heat detectors and
    manual call points
•   Two fused sounder circuits, monitored for open and short circuits
•   Mutable fault monitoring for mains, power supply unit, battery, sounders and
    detectors
•   1 amp power supply unit, with space for up to 6 A.H. sealed lead acid
    batteries
•   5 amp alarm relay output and 24 volt DC output
•   High brightness dual LED indicators and touch sensitive controls
•   This dual zone control has been designed to conform with the requirements
    of BS 3116 and BS 5839
•   For ease of installation and service, connections are made to a small rear mounted printed circuit board
    which also holds the battery and sounder fuses. The metal case has three point key-slot fixing with 20 mm     conduit trunking top and bottom entry points
•   The detection zones are monitored with an end of line resistor to give fault and fire indications. They will
    monitor upto 35 low current smoke detectors and an infinite number of manual call points or other OC
    devices
•   The sounder circuits are fused and monitored for open and short circuits with an end of line resistor. Upto     40 low current sounders (25 mA) may be fitted
•   A voltage free 5 A relay is provided for door closers, signaling etc
•   A monitored fused 24 V D.C. output is provided
•   The power supply is fully monitored for failure, mains failure, battery failure, low voltage and battery
    disconnection
•   The user controls are enabled by means of a security key-switch
•   Mute Sounders - mutes sounders and fault warning
•   Sound Alarm - to evacuate building or resound alarm
•   Reset (Test) - to reset control and detectors and test control
•   Indications are provided for mains power, common fire, zone fire, common fault, zone fault, sounder fault
    and power fault
•   Audible indications are provided for fire and fault
•   Printed circuit boards are available as new for spares

FCC 3000W - Multi Zone Fire Alarm Controls


Features:
•   This control panel has been designed for the professional installer to
    conform with the requirements of BS 3116 and BS 5839, 1988
•   The master control unit can have from one to four zones extendable
    internally using plug in zone cards. The master control may be extended with     10-zone extender units and plug in zone cards
•   The modular system allows minimum stocking requirements, ease of service
    and maintenance, ease of system extension and future system upgrades
•   Plug in Bell delay modules
•   Non Latch test facility
•   Fire and Auxiliary relay outputs
•   Zone isolation
•   Add on gas extinguishing control units are available to extend the system or an area within the system to
    a double knock automatic gas release system
•   Outputs for repeater panels, communicators, door closers extractors etc
•   The detection zones are monitored with an end of line resistor to give fault and fire indications. They will
    monitor up to 35 low current smoke detectors and an infinite number of manual call points or other Open
    Circuit devices
•   The sounder circuits are fused and monitored for open and short circuits with an end of line resistor. Up
    to 40 low current sounders (25 mA) may be fitted
•   The power supply is fully monitored for failure, mains failure, battery failure, low voltage and battery
    disconnection
•   The user controls are enabled by means of a security keys-witch
•   Mute Sounders - mutes sounders and fault warning
•   Sound Alarm - to evacuate building or resound alarm
•   Reset (Test) - to reset control and detectors and test control
•   Indications are provided for mains power, common fire, zone fire, common fault, zone fault, sounder fault
    and power fault
•   Audible indications are provided for fire and fault
•   Printed circuit boards are available as new for spares
 